a bar primary 1500/5 ct has a secondary winding resistance and leakage reactance of (0.5+j0.5)ohm if the flux density has not be exceed 1.4tesla at 10 times the rated symmetrical current determined the maximum value of the resistive burden which can be connected, the core cross section is 30cm2,your power system's relaying information source,GENERATOR - TRANSFORMER VOLTS PER HERTZ PROTECTION,CURRENT TRANSFORMER (CT) BURDEN SAMPLE CALCULATION,OVER EXCITATION PROTECTION FOR POWER TRANSFORMER BASICS AND TUTORIALS,NON DIRECTIONAL OVERCURRENT RELAY SCHEMES FOR TRANSMISSION LINES,REMOTE TRIPPING OF CIRCUIT BREAKERS BASICS. All rights reserved.This blog will cover: Which the errors of the instrument transformer raise above the tolerable specified error limit. Make sure the total burden does not exceed the specified limits for the CT.

It is generally expressed in VA (volt-ampere).

Current transformer burden is defined as the load connected across its secondary. All instruments that use a current transformer to measure line current must terminate the CT with a resistance (impedance in same case which means there is some inductance involved).A CT supplier should be given the burden when ordering. product updates Innovation and Accuracy in Current Measurement.Why do you care about burden when ordering current transformers?Many of our customers regularly request quotes for standard and custom 5A ratio type current transformers but only ask for the window size and the input current with no knowledge of the “burden”. The measuring instrument can be an analog or digital energy meter, a data logger or a recorder. industry news Instrument transformers are basically the transformers like normal purpose transformers, instrument transformers have also to carry electrical loads. That means when we connect any burden to the secondary of the instrument transformer above 15KV may cause error beyond the limits of errors specified for 0.1 accuracy class. continuing education topics Figure 2 – Derivation of equivalent circuit of a current transformer A study of the final equivalent circuit of Figure 2 (c), taking note of the typical component values, reveals all the properties of a current transformer.

The burden is specified as VA or resistance (or impedance). Each of these instruments has its own VA consumption rating.

The measuring instrument can be an analog or digital energy meter, a data logger or a recorder. Again watt meters, power factor meters and energy meters have VA rating of high VA each.We normally express the burden of different relays in VA. But for selecting appropriate current transformers for differential and distance protections, we need to know the ohmic values of these relays.

The system is considered to be carrying rated current (300A) and the CT is feeding a burden of 10VA. But in current transformer or.For example suppose a current transformer has accuracy class 0.1 and burden of the instrument transformer is 15KV. It varies with turns ratio, desired output and current rating of the primary.Can you please clear the resistance value for mPN-SCT-0400-025,Copyright © Magnelab.

So, to keep the error within tolerance limit we need to operate the instrument transformer below 15VA.The total burden of an instrument transformer may be due to connected voltmeter, watt meters.The metering system consists of ammeters, voltmeters, watt meters, power factor maters, energy meters etc. So, like other general purpose transformers instrument transformer (current transformers and,In normal power transformer the volt ampere rating is specified depending on the allowable temperature rise.

3. For example, suppose a 1A relay has VA rating of 6VA.

It can be seen that: As the rated secondary current in case of CT is 5 ampere so its burden can also be expressed in terms of impedance at rated secondary current at given power factor (generally 0.75 lagging).

Refer to the table at the right to determine the resistance, in ohms or VA, of the wires that connect the secondary of the current transformer to the device. Then the ohmic burden of these relay will be 6/1.The data sheet gives the value of the resistance per unit length of each conductor in a control cable. All instruments that use a current transformer to measure line current must terminate the CT with a resistance (impedance in same case which means there is some inductance involved). For example, a standard ammeter has the VA rating of 3VA.

upcoming tradeshow schedule so you can stop by and see us in person

Measure the length of the wire between the current transformer and the burden (i.e. c) The primary current rating per phase from distribution transformer d) The secondary current rating usually 1 A or 5 A e) The rated real output power This output power is also called burden.

and much more...Advantages & Applications of Rogowski Coils,APPLICATION NOTE – SCT SERIES: INTRODUCTION TO THE SCT SERIES OF CURRENT TRANSFORMERS,New Switch Gear Current Transformer (Coming Soon),ENVIRONMENTALLY FRIENDLY COMPANY LOOKING TO EXPAND,Measurement of Below 20 Amps with Magnelab RopeCT and Integrator,JUST RELEASED UL-Listed Current Transformers,Magnelab Exhibits at DistribuTECH in New Orleans,Rogowski Coil Linearity and Accuracy with and without Integrators,Magnelab’s 50th Anniversary Celebration Video Link,Video – Magnelab UL Listed Rogowski Coils,Magnelab’s First Line of UL Listed Rogowski Coils,Real-Time Electricity Savings for Schools Using Magnelab Current Transformers,Magnelab at World Energy Engineering Congress (WEEC) September 27-28,Magnelab at Sensors Expo June 28-29, 2017,Magnelab at West Coast Energy Management Congress June 7th and 8th, 2017,How to Determine Core Size in Current Transformers,Contact Magnelab to Help Alleviate Equipment Failure and Save Money with Monitoring.Tracking how Electric Vehicles charging effect residential power usage.The benefits of high quality electrical usage interval data,Explanation of Accuracy Specifications for Current Transformers,Current to Voltage vs Current to Current Transformers.

Technically, the total burden for a CT is the internal winding resistance, the connecting lead resistance and the measuring instrument input resistance.Below is a table of CT burdens that you can use to tell your CT supplier full information about what you need in addition to input current and window opening:Could you please let me know which standards (IEC or IEEE or BS) apply on the CT Burdens (VA) vs Z (Ohms) table you provided above (under Products).You can calculate the VA burden in case you know the Z(ohms) as follow:For example, if Z=.002 ohms, Burden=5*5*.002=.05 VA.Should the burden of the CTs be equal to the burden of the measuring being used (e.g digital energy meter).The burden of the CT is the resistive load used to create the voltage on the output. The burden needs to be calculated for each measurement setup.